Bacterial contamination of inside atmospheres like surgery rooms and emergency departments can be determined by active or passive sampling and by counting colony numbers per cubic meter of air or square meters of floor area. Devices used to sample airborne bacteria mainly rely on different principles namely, impaction, impingement, filtration, suction and electrostatic precipitator by cultivation and non-cultivation methods (
1). Nevertheless most of the studies on bio-aerosols of inside atmospheres have been based on culturing methods (
11). In this study, both active sampling and culturing were used for determining qualitative and quantitative contamination level. On the other hand, there are different kinds of active sampling (
12,
13) for which a suitable sampler tool is used on the basis of availability and influence. However, Pavicic et al. have suggested that eight-step Anderson is better than two-step (
14).
In this descriptive-analytical study, instruction number NIOSH 0800 was used for sampling (
15). A total of 72 samples were collected from three operating rooms and three rooms in the emergency department of an educational hospital during 2012. On the first day of every month, one sample was collected from every room at the beginning of the morning shift (7-8 a.m.). Plates were located one meter above the floor and one meter far from obstacles and walls to collect the samples. Plates consisting of blood agar, MacConkey agar and brain-heart infusion agar (BHI) (Germany's Merck company) were exposed to the air of the study area for 10 minutes by sampling axis including one-story Anderson impactor (flow rate 28.1 litter per minutes, England) and SIBATA pump (Sibata Scientific Technology Ltd, Japan). Then, the lid of the plate was closed by Para-film and was transferred to the microbiology laboratory where the plates were placed in a 35°C incubator for 24-48 hours.
Bacterial colonies were counted and examined by warm coloring and biochemical differential tests. Finally, the result was recorded in the bacterial report. Also eosin methylene-blue lactose sucrose (EMB, Merck KGaA, Darmstadt, Germany), coagulase test, Salmonella-Shigella agar (Merck KGaA, Darmstadt, Germany) and methyl red and Voges-Proskauer (IMVIC) test were performed for differential tests. Although many biological agents that may cause diverse health effects have not been identified yet and maximum limits of various bio-aerosols has not been determined individually, recommended maximum limits set by the National Institute of Occupational Safety and Health (NIOSH) and the American Conference of Governmental Industrial Hygienists (ACGIH) is 1000 cfu/m
3 for the total number of bio-aerosol particles, with culturable counts for total bacteria not exceeding 500 cfu/m
3 (
16). The ACGIH also recommended < 100 cfu/m
3 for hospitals (
17). Furthermore, for hospital air, WHO suggested relatively relaxed limits of 100 cfu/m
3 for bacteria and 50 cfu/m
3 for fungi although many facilities fail to meet this range (
18). Descriptive statistics was reported as mean ± SD. In order to compare mean amount of bacteria in the emergency department and operating rooms, Mann-Whitney U test was used. Kruskal-Wallis test compared mean amount of bacteria for different seasons.